一、Characteristics
of Shambala heat recovery
ventilation :
1 Complete heat
recovery and high efficiency
energy saving
The use of high-tech
nanometer film technology,
horizontal-reversed convection
technology, antistatic
maintenance-free technology,
noise damping technology
makes Shambala heat recovery
ventilation unit achieve
a breakthrough in energy
recovery efficiency by
more than 72%. The significant
energy recovery will
not only reduce investments
on air conditioner capacity
and also will reduce
the huge running costs
of the entire air-conditioning
system.
2 Humanized
product design
1) Super low noise design:
Shanbala heat recovery
ventilation unit adopts
super low noise ventilator,
and takes the high efficiency
noise-damping technology.
2) Maintenance-free design:
The special designed
air passage make the
air flow easily pass
through it, and can be
used continuously for
long time, realizing
the heat exchanger corpus
without maintenance need.
3) Compact super thin
design for easier installation
and construction space
saving.
4) Precision making alloyed
aluminum frames. Using
high quality steel sheets,
environment-protective
materials and alloyed
aluminum frames. Treating
the surface with static
electricity painting
to get elegant appearance.
5 )Air filtering design:
The products are equipped
inside with specialized
air filter to ensure
the air coming into house
is fresh.
3 Bypass system-prolongs
the life
With the special design
of bypass function, Shambala
heat recovery ventilation
unit can fully use the
natural energy in spring
and autumn seasons, inhale
fresh air directly to
keep the indoor air clean,
no need to pass through
heat exchanger, thus
it prolongs the life
of the machines.
二、products
series
Model explanation
Nomenclature AHE-50WB
Distinguish code: B-Super
thin type, Standard
type without mark
Pattern code: W-horizontal
L-vertical K-cassette
type G-wall mounted type
Rated Air floe volume:
numberx10m3/h
Product code: Air to
air heat exchanger
Appearance & installation
size (mm)
Model |
A |
B |
C |
D |
E |
F |
G |
H |
I |
Фd |
AHE-15WB |
400 |
545 |
430 |
406 |
642 |
264 |
30 |
200 |
486 |
100 |
AHE-15W |
505 |
885 |
559 |
815 |
1042 |
252 |
112 |
270 |
619 |
100 |
AHE-25W |
670 |
885 |
720 |
815 |
1075 |
342 |
112 |
270 |
784 |
150 |
AHE-35W |
810 |
885 |
860 |
815 |
1075 |
482 |
112 |
270 |
924 |
150 |
AHE-50W |
904 |
962 |
960 |
890 |
1128 |
500 |
380 |
310 |
1018 |
200 |
AHE-80W |
885 |
1322 |
936 |
1252 |
1488 |
430 |
172 |
396 |
1000 |
250 |
AHE-100W |
1132 |
1322 |
1186 |
1252 |
1488 |
681 |
172 |
396 |
1246 |
250 |
Performance
parameter
Model |
Power
(V/HZ) |
Volume
(m3/h) |
Static
pressure
outside the machine
(pa) |
Heat
recovery rate
(%) |
Rated
power
(W) |
Noise
dB(A) |
Weight
(kg) |
Carton
size
(cm) |
AHE-15WB |
~220
50/60 |
150/150/110 |
60/45/30 |
65/65/68 |
40/38/32 |
24/23/22 |
18 |
60×50×23 |
AHE-15W |
~220
50/60 |
150/150/115 |
75/58/34 |
71/71/75 |
72/60/50 |
26/24/22 |
19 |
112×63×35 |
AHE-25W |
~220
50/60 |
250/250/160 |
85/65/30 |
71/71/75 |
105/100/80 |
27/26/22 |
21 |
112×84×35 |
AHE-35W |
~220
50/60 |
350/350/270 |
90/60/30 |
71/71/75 |
140/125/115 |
31/29/25 |
31 |
112×110×35 |
AHE-50W |
~220
50/60 |
500/500/360 |
100/60/30 |
71/71/75 |
190/175/150 |
33/31/27 |
50 |
117×116×39 |
AHE-80W |
~220
50/60 |
800/800/625 |
150/100/40 |
71/71/75 |
320/273/205 |
38/36/32 |
61 |
153×105×17 |
AHE-100W |
~220
50/60 |
1000/780/650 |
115/75/35 |
71/71/75 |
450/375/330 |
39/37/33 |
80 |
153×132×17 |
Appearance & installation
size (mm)
Model |
A |
B |
C |
D |
E |
F |
H |
h |
L×R |
AHE-150WB |
1020 |
1480 |
944 |
1443 |
1580 |
430 |
558 |
360 |
230×220 |
AHE-200WB |
1220 |
1480 |
1144 |
1443 |
1580 |
530 |
558 |
360 |
300×220 |
AHE-250WB |
1420 |
1620 |
1344 |
1583 |
1720 |
630 |
558 |
360 |
320×250 |
AHE-300WB |
1620 |
1850 |
1544 |
1813 |
1950 |
730 |
558 |
360 |
356×305 |
Performance
parameter
Model |
Power
(V/HZ) |
Volume
(m3/h) |
Static
pressure
outside the machine
(pa) |
Heat
recovery rate
(%) |
Rated
power input
(W) |
Noise
dB(A) |
Weight
(kg) |
AHE-150WB |
Three
Phase
~380/50/60 |
1500 |
180 |
70 |
0.25×2 |
46 |
90 |
AHE-200WB |
Three
Phase
~380/50/60 |
2000 |
200 |
70 |
0.45×2 |
46.5 |
110 |
AHE-250WB |
Three
Phase
~380/50/60 |
2500 |
250 |
70 |
0.55×2 |
54 |
180 |
AHE-300WB |
Three
Phase
~380/50/60 |
3000 |
250 |
70 |
0.8×2 |
58 |
252 |
Appearance & installation
size (mm)
Model |
A |
B |
C |
D |
E |
F |
H |
h |
L×R |
AHE-150W |
882 |
1322 |
1005 |
1250 |
330 |
431 |
200 |
800 |
250×600 |
AHE-200W |
1132 |
1322 |
1256 |
1250 |
330 |
681 |
200 |
800 |
250×600 |
AHE-250W |
1238 |
1700 |
1198 |
1640 |
1800 |
550 |
610 |
805 |
320×250 |
AHE-300W |
1458 |
1700 |
1418 |
1640 |
1800 |
660 |
610 |
805 |
320×250 |
AHE-400W |
1898 |
1850 |
1862 |
1813 |
1950 |
889 |
610 |
805 |
310×310 |
Performance
parameter
Model |
Power
(V/HZ) |
Volume
(m3/h) |
Static
pressure
outside the machine
(pa) |
Heat
recovery rate
(%) |
Rated
power
(W) |
Noise
dB(A) |
Weight
(kg) |
AHE-150W |
Three
Phase
~380 50/60 |
1500/1200/980 |
135/100/60 |
70/72/75 |
887/880/860 |
48/46/43 |
155 |
AHE-200W |
Three
Phase
~380 50/60 |
2000/1500/1300 |
90/70/45 |
70/72/75 |
920/750/690 |
48/46.5/43 |
180 |
AHE-250W |
Three
Phase
~380 50/60 |
2500 |
250 |
70 |
1.1(KW) |
54 |
185 |
AHE-300W |
Three
Phase
~380 50/60 |
3000 |
250 |
70 |
1.6(KW) |
58 |
252 |
AHE-400W |
Three
Phase
~380 50/60 |
4000 |
320 |
70 |
2.6(KW) |
60 |
330 |
Appearance & installation size (mm)
Model |
A |
B |
C |
D |
E |
F |
G |
H |
L×R |
L1×R1 |
AHE-400L |
1850 |
790 |
1930 |
890 |
50 |
835 |
1600 |
1680 |
350×400 |
320×500 |
AHE-500L |
2250 |
790 |
2332 |
890 |
50 |
1125 |
1600 |
1680 |
350×400 |
320×600 |
AHE-600L |
2550 |
790 |
2630 |
890 |
50 |
1265 |
1600 |
1680 |
400×500 |
320×700 |
AHE-800L |
1850 |
1700 |
1950 |
1500 |
100 |
1290 |
2455 |
2555 |
1250×500 |
320×500 |
AHE-1000L |
2250 |
1700 |
2350 |
1500 |
100 |
1330 |
2535 |
2635 |
1250×500 |
400×500 |
Performance
parameter
Model |
Power
(V/HZ) |
Volume
(m3/h) |
Static
pressure
outside the machine
(pa) |
Heat
recovery rate
(%) |
Rated
power
(W) |
Noise
dB(A) |
Weight
(kg) |
AHE-400L |
Three
Phase
~380 50/60 |
4000 |
320 |
72 |
1.1×2 |
64 |
350 |
AHE-500L |
Three
Phase
~380 50/60 |
5000 |
320 |
72 |
1.5×2 |
65 |
385 |
AHE-600L |
Three
Phase
~380 50/60 |
6000 |
320 |
72 |
1.8×2 |
66 |
650 |
AHE-800L |
Three
Phase
~380 50/60 |
8000 |
350 |
72 |
2.2×2 |
68 |
950 |
AHE-1000L |
Three
Phase
~380 50/60 |
10000 |
350 |
72 |
3.0×2 |
69 |
1150 |
Package air-to-air
heat exchanger ventilation
unit
Model |
L |
H |
L1 |
A |
B |
H1 |
AHE-1000 |
2250 |
1630 |
560 |
500 |
1108 |
100 |
AHE-1500 |
3300 |
1630 |
838 |
1000 |
1137 |
100 |
AHE-2000 |
4400 |
1600 |
1112 |
800 |
1137 |
100 |
AHE-3000 |
4400 |
2375 |
1112 |
1000 |
1912 |
100 |
AHE-4000 |
4400 |
3150 |
1112 |
1000 |
2687 |
140 |
AHE-5000 |
4400 |
3925 |
1112 |
1000 |
3462 |
140 |
Function parameter
table
Model |
Rated
fresh air flow(m3/h) |
Heat
recovery ratio
(%) |
Static
pressure difference(Pa) |
Weight(Kg) |
AHE-1000 |
10000 |
72 |
230 |
700 |
AHE-1500 |
15000 |
72 |
240 |
950 |
AHE-2000 |
20000 |
72 |
270 |
1300 |
AHE-3000 |
30000 |
72 |
260 |
1950 |
AHE-4000 |
40000 |
72 |
280 |
2600 |
AHE-5000 |
50000 |
72 |
300 |
3250 |
|